Reverse Osmosis Systems-RE series

$0.00

RE series reverse osmosis systems are used for low volume applications where feedwater TDS is below 1,000ppm.

Category: SKU: RE

Description

Overview

RE series reverse osmosis systems are used for low volume applications where feedwater TDS is below 1,000ppm.

RO pressure vessels are non-metallic PVC with high performance RO membranes.

The frame is electro-polished 304 grade stainless-steel for corrosion resistance.

Metal wetted surfaces are 316 grade stainless steel or corrosion resistant brass.

Continual monitoring of feedwater pressure, RO permeate quality and storage tank level is performed by the controller and permeate quality is displayed continuously.

Options are available for higher TDS feedwaters, external feedwater break tanks and automatic feedwater pressure booster pumps.

 

Features

RO System Features

  • Stainless steel frame open frame
  • Compact high-pressure membrane housings
  • High pressure S/S braided flexible hose
  • Rotary vane pump
  • Micro-processor based controller
  • Low feedwater pressure sensor
  • Permeate quality sensor & conductivity display
  • Storage tank level sensor input
  • Permeate and reject flow rotameters
  • Adjustable pressure regulator valve
  • Pressure gauges

Specifications

RE Series specifications

RE250

RE500

Capacity (lpd)

800

1500

Operating pressure (kPa)

1000-1350

Pre-filtration

20″housings with 5/10µm or 5µm/carbon filter elements

Pressure pump

Rotary vane type, brass, 0.375kW

Membrane type

Thin film, high performance, FRP outer wrap

Size x Unit

2521 x 1

2521 x 2

Pressure vessel

High pressure PVC

Size x Unit

2521 x 1

2521 x 2

Flow meters

Permeate and reject flow stream

Pressure gauges

Inlet and pump discharge/membrane inlet

Water quality display

TDS meter with LCD display

Electrical controls

Microprocessor based with circuit breakers

Frame

Electropolished stainless steel

Dimensions (excluding filters)

330mm x 330mm x 920mm (LWH)

 

Operating conditions

Max Operating pressure

1350kPa

Maximum recovery

70%

Nominal rejection

98-99%

Operating temperature

+5 to 45°C

 

Feedwater requirements

pH

3.0 to 10.0

TDS/FAC

< 1,000 ppm/<0.1ppm

Turbidity

< 1.0 NTU

SDI/Hardness

< 3.0/<5ppm